MTP/MPO fiber optic jumpers are usually deployed in relatively small spaces, such as telecommunications distribution boxes, data center cabinets, etc. In these cases, the fiber core needs to have a curved arc. Inferior fiber core bending usually results in loss of signal and thus interruption of transmission. But brand optical fiber is different. For example, Corning optical fiber can greatly improve bending performance, minimize signal loss, and achieve faster and more efficient optical fiber wiring and installation. Therefore, the brand fiber core is very important for MTP/MPO fiber patch cords.
MPO Connector | Standard Loss SM Connector | Low Loss SM Connector | Standard Loss MM Connector | Low Loss MM Connector | |||
End-surface Type | APC | PC | APC | PC | PC | PC | |
Insertion Loss(dB) | General | 0.35 | 0.35 | 0.2 | 0.2 | 0.35 | 0.3 |
Max | 0.7 | 0.7 | 0.35 | 0.35 | 0.7 | 0.5 | |
Return Loss(dB) | 60 | 50 | 60 | 50 | 20 | 20 | |
interchangeability(dB) | ≤0.20 | ||||||
Durability(dB) | <0.20dB (500 Matings, per EIA-455-21A) | ||||||
Tensile Strength(dB) | ≤0.3 (Max 66N) | ||||||
Temperature Cycle(dB) | ≤0.5 (-40~+75°C, 21 Cycles) | ||||||
Operation Temperature(°C) | -20~+70 | ||||||
Storage Termperature(°C) | -40~+85 |
Corning or YOFC Fiber
US CONEC MPO connector
Fiber counts can be customized
Male or female can be customized
8-core MTPMPO branch fiber jumper realizes direct connection from 40G SR4 to 10G SR
12-core MTPMPO backbone jumper and 40G adapter panel realize 10G to 40G network upgrade
40G SR4 and 12-core MTPMPO trunk fiber jumper directly
IL/RL test
3D test
Temperature cycle
1. MPO standard compliant multifiber connector
2. Connector’s design complies with IEC 61754-7 standards
3. 8, 12, or 24 fiber connector terminations and assemblies
4. Meet TIA/EIA 604-5 Type MPO
5. LSZH, LZOH, OFNP, OFNR cable jacket types selection
6.100% Optic test
7. Push-pull connector mating assures secure connections
8. Precision guide pin assures fiber alignment at mating
9. Most economical solution for mass-termination of fibers
The MPO/MTP jumper provided by OPTICO meets the working environment of -40~85℃, with an average of more than 1000 insertion and removal experiments, with stable performance and reliable quality.
Welcom to consult.
MPO Connector | Standard Loss SM Connector | Low Loss SM Connector | Standard Loss MM Connector | Low Loss MM Connector | |||
End-surface Type | APC | PC | APC | PC | PC | PC | |
Insertion Loss(dB) | General | 0.35 | 0.35 | 0.2 | 0.2 | 0.35 | 0.3 |
Max | 0.7 | 0.7 | 0.35 | 0.35 | 0.7 | 0.5 | |
Return Loss(dB) | 60 | 50 | 60 | 50 | 20 | 20 | |
interchangeability(dB) | ≤0.20 | ||||||
Durability(dB) | <0.20dB (500 Matings, per EIA-455-21A) | ||||||
Tensile Strength(dB) | ≤0.3 (Max 66N) | ||||||
Temperature Cycle(dB) | ≤0.5 (-40~+75°C, 21 Cycles) | ||||||
Operation Temperature(°C) | -20~+70 | ||||||
Storage Termperature(°C) | -40~+85 |